A 15-KVA, 2400/240-V transformer is to be tested to determine its excitation branch components, its series impedances and its voltage regulation. The following test data have been taken from the primary side of the transformer: Open- circuit test Voc = 2400 V loc = 0.25 A Poc = 50 W Short-circuit test Vsc = 48 V Isc = 6.0 A Psc = 200 W Pg103 The data have been taken by using the connections of open-circuit test and short-circuit test a. Find the equivalent circuit of this transformer referred to the high-voltage side. b. Find the equivalent circuit of this transformer referred to the low-voltage side. c. Calculate the full-load voltage regulation at 0.8 lagging power factor and 0.8 leading power factor. d. What is the efficiency of the transformer at full load with a power factor of 0.8 lagging?

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter3: Power Transformers
Section: Chapter Questions
Problem 3.5MCQ: For an ideal 2-winding transformer, an impedance Z2 connected across winding 2 (secondary) is...
icon
Related questions
Question
Assignment 3
A 15-KVA, 2400/240-V transformer is to be
tested to determine its excitation branch
components, its series impedances and its
voltage regulation. The following test data
have been taken from the primary side of the
transformer:
Short-circuit test
Open- circuit test
Voc = 2400 V
loc = 0.25 A
Poc = 50 W
Vsc = 48 V
Isc = 6.0 A
Psc = 200 W
Pg103
The data have been taken by using the connections
of open-circuit test and short-circuit test
a. Find the equivalent circuit of this transformer
referred to the high-voltage side.
b. Find the equivalent circuit of this transformer
referred to the low-voltage side.
c. Calculate the full-load voltage regulation at 0.8
lagging power factor and 0.8 leading power factor.
d. What is the efficiency of the transformer at full
load with a power factor of 0.8 lagging?
Transcribed Image Text:Assignment 3 A 15-KVA, 2400/240-V transformer is to be tested to determine its excitation branch components, its series impedances and its voltage regulation. The following test data have been taken from the primary side of the transformer: Short-circuit test Open- circuit test Voc = 2400 V loc = 0.25 A Poc = 50 W Vsc = 48 V Isc = 6.0 A Psc = 200 W Pg103 The data have been taken by using the connections of open-circuit test and short-circuit test a. Find the equivalent circuit of this transformer referred to the high-voltage side. b. Find the equivalent circuit of this transformer referred to the low-voltage side. c. Calculate the full-load voltage regulation at 0.8 lagging power factor and 0.8 leading power factor. d. What is the efficiency of the transformer at full load with a power factor of 0.8 lagging?
Expert Solution
steps

Step by step

Solved in 8 steps with 2 images

Blurred answer
Knowledge Booster
Single phase transformer
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning