The dc backup generator that supports the local servers in the centre directly supplying a dc voltage, is a 200 V compound generator with the following circuit parameters: Armature resistance Ra: 0.1 2 Shunt resistance: 40 Series resistance: 0.05 2 The total load of the servers is equal to 10 kW and needs to be maintained to 200 V. You can ignore the armature reactance. The voltage drop across each brush of the motor is equal to 1 V. ● (Q2, What is the EMF and the armature current of the generator if the generator is connected as a long-shunt compound generator. What is the EMF and the armature current of the generator if the generator is connected as a short-shunt compound generator. (Q21) (Q2g Your colleague, Bruce, recommends using a series de generator instead. Under what circumstances would his suggestion make a better alternative?

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter12: Power System Controls
Section: Chapter Questions
Problem 12.7P
icon
Related questions
Question
100%
The dc backup generator that supports the local servers in the centre directly supplying a dc voltage, is a 200 V
compound generator with the following circuit parameters:
Armature resistance Ra: 0.1 2
Shunt resistance: 40
Series resistance: 0.05 2
The total load of the servers is equal to 10 kW and needs to be maintained to 200 V.
You can ignore the armature reactance. The voltage drop across each brush of the motor is equal to 1 V.
●
(Q2,
What is the EMF and the armature current of the generator if the generator is connected as a
long-shunt compound generator.
What is the EMF and the armature current of the generator if the generator is connected as a
short-shunt compound generator.
(Q21)
(Q2g
Your colleague, Bruce, recommends using a series de generator instead. Under what
circumstances would his suggestion make a better alternative?
Transcribed Image Text:The dc backup generator that supports the local servers in the centre directly supplying a dc voltage, is a 200 V compound generator with the following circuit parameters: Armature resistance Ra: 0.1 2 Shunt resistance: 40 Series resistance: 0.05 2 The total load of the servers is equal to 10 kW and needs to be maintained to 200 V. You can ignore the armature reactance. The voltage drop across each brush of the motor is equal to 1 V. ● (Q2, What is the EMF and the armature current of the generator if the generator is connected as a long-shunt compound generator. What is the EMF and the armature current of the generator if the generator is connected as a short-shunt compound generator. (Q21) (Q2g Your colleague, Bruce, recommends using a series de generator instead. Under what circumstances would his suggestion make a better alternative?
Expert Solution
steps

Step by step

Solved in 5 steps with 18 images

Blurred answer
Knowledge Booster
Magnetic moment
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning
Delmar's Standard Textbook Of Electricity
Delmar's Standard Textbook Of Electricity
Electrical Engineering
ISBN:
9781337900348
Author:
Stephen L. Herman
Publisher:
Cengage Learning