identical, 3-phase, Y-connected alternators A and B share equally a load of 10MW at 33kV at 0.8pf lagging. The synchronous reactance of each machine is 4 ohms per phase and the armature resistance is negligible. Alternator A has its field excitation adjusted to carry 125A lagging current. What is the current supplied

Delmar's Standard Textbook Of Electricity
7th Edition
ISBN:9781337900348
Author:Stephen L. Herman
Publisher:Stephen L. Herman
Chapter31: Three-phase Alternators
Section: Chapter Questions
Problem 1RQ: What conditions must be met before two alternators can be paralleled together?
icon
Related questions
Question
Two identical, 3-phase, Y-connected alternators A and B share equally a load of 10MW at 33kV at 0.8pf lagging. The synchronous reactance of each machine is 4 ohms per phase and the armature resistance is negligible. Alternator A has its field excitation adjusted to carry 125A lagging current. What is the current supplied by alternator B?
Expert Solution
steps

Step by step

Solved in 2 steps with 2 images

Blurred answer
Knowledge Booster
Synchronous Generator
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.