The load at a certain factory consists of the following: 10 kW, pf = 0.6 lagging 15 kW, rf = 0.5 lagging 25 kVA, pf = 0.75 lagging 15 kVAR, pf = 0.8 lagging 22 kW 5 kVAR, pure inductance Total True Power = 85.75 kW Total Reactive Power = 58.5295 kVAr Total Apparent Power = 103.8208 KVA 1. The power factor is to be corrected to 0.95 lagging. If resistive heating units were used instead, determine the real power rating of these devices. Ans = 92.3222 2. The power factor is to be corrected to 0.95 lagging. If a synchronous motor is to be used instead, determine the real power rating of this motor if its
The load at a certain factory consists of the following: 10 kW, pf = 0.6 lagging 15 kW, rf = 0.5 lagging 25 kVA, pf = 0.75 lagging 15 kVAR, pf = 0.8 lagging 22 kW 5 kVAR, pure inductance Total True Power = 85.75 kW Total Reactive Power = 58.5295 kVAr Total Apparent Power = 103.8208 KVA 1. The power factor is to be corrected to 0.95 lagging. If resistive heating units were used instead, determine the real power rating of these devices. Ans = 92.3222 2. The power factor is to be corrected to 0.95 lagging. If a synchronous motor is to be used instead, determine the real power rating of this motor if its
Electricity for Refrigeration, Heating, and Air Conditioning (MindTap Course List)
10th Edition
ISBN:9781337399128
Author:Russell E. Smith
Publisher:Russell E. Smith
Chapter7: Alternating Current, Power Distribution, And Voltage Systems
Section: Chapter Questions
Problem 7RQ
Related questions
Question
The load at a certain factory consists of the following:
10 kW, pf = 0.6 lagging
15 kW, rf = 0.5 lagging
25 kVA, pf = 0.75 lagging
15 kVAR, pf = 0.8 lagging
22 kW
5 kVAR, pure inductance
Total True Power = 85.75 kW
Total Reactive Power = 58.5295 kVAr
Total Apparent Power = 103.8208 KVA
1. The power factor is to be corrected to 0.95 lagging. If resistive heating units were used instead, determine the real power rating of these devices. Ans = 92.3222
2. The power factor is to be corrected to 0.95 lagging. If a synchronous motor is to be used instead, determine the real power rating of this motor if its power factor is 0.6 leading. Ans = 18.257
Expert Solution
This question has been solved!
Explore an expertly crafted, step-by-step solution for a thorough understanding of key concepts.
Step by step
Solved in 5 steps with 5 images
Knowledge Booster
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.Recommended textbooks for you
Electricity for Refrigeration, Heating, and Air C…
Mechanical Engineering
ISBN:
9781337399128
Author:
Russell E. Smith
Publisher:
Cengage Learning
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning
Electricity for Refrigeration, Heating, and Air C…
Mechanical Engineering
ISBN:
9781337399128
Author:
Russell E. Smith
Publisher:
Cengage Learning
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning