Three-Phase, 50 Hz, 220 KV Transmission Line consists of conductors of 1.2 cm radius spaced 2 meters at the corners of an equilateral triangle. Calculate the Corona Power Loss per km of the line at a Temperature of 20ºC and Barometric Pressure of 72.2 cm of Hg. Take the Surface Factor of the conductor as 0.96

Power System Analysis and Design (MindTap Course List)
6th Edition
ISBN:9781305632134
Author:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Chapter4: Transmission Line Parameters
Section: Chapter Questions
Problem 4.13P: A single-phase overhead transmission line consists of two solid aluminum conductors having a radius...
icon
Related questions
icon
Concept explainers
Question
A Three-Phase, 50 Hz, 220 KV Transmission Line consists of conductors of 1.2 cm radius spaced 2 meters at the corners of an equilateral triangle. Calculate the Corona Power Loss per km of the line at a Temperature of 20ºC and Barometric Pressure of 72.2 cm of Hg. Take the Surface Factor of the conductor as 0.96
Expert Solution
trending now

Trending now

This is a popular solution!

steps

Step by step

Solved in 3 steps with 3 images

Blurred answer
Knowledge Booster
Transmission line parameter
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, electrical-engineering and related others by exploring similar questions and additional content below.
Similar questions
  • SEE MORE QUESTIONS
Recommended textbooks for you
Power System Analysis and Design (MindTap Course …
Power System Analysis and Design (MindTap Course …
Electrical Engineering
ISBN:
9781305632134
Author:
J. Duncan Glover, Thomas Overbye, Mulukutla S. Sarma
Publisher:
Cengage Learning