Textbook Question
Book Icon
Chapter 39, Problem 1RQ

Name two requirements that must be met before a motor can be used for wye–delta starting.

Expert Solution & Answer
Check Mark
To determine

The requirements that must be met before the motor is used for the wye delta starting.

Explanation of Solution

Consider that delta starting is often used to reduce the inrush current in to the motor and at the starting to reduce the starting torque.

Consider the requirement for the motor to be used for the wye delta starting is,

The motor designed for the stator winding must be in delta during the running period.

The leads of the stator winding should be accessible.

Therefore, the requirements of the motor to start by the use of the wye delta starting is discussed.

Want to see more full solutions like this?

Subscribe now to access step-by-step solutions to millions of textbook problems written by subject matter experts!
Students have asked these similar questions
4. Describe two type of starting system principles and draw the basic starting circuit
A 50 Hz pump drive requires a torque of 70 Nm approx. at 1450 rpm approx. for 1 minute followed by 5 minutes running unloaded. This cyclic pattern is repeated continuously. The motor is to be selected from a range of general-purpose motors with continuous ratings of 2.2, 3, 4, 5.5, 7.5, 11, 15 and 20 kW. The motors have a pull-out torque of 200%. 1. Select the pole number. 2. Calculate the continuous power rating. 3. 4. Calculate the required power rating given the pull out torque rating. Estimate the slip when the motor drives the pump at the required speed. Choose the motor from the range of options that is most fit for purpose. 5. Enter your answers in the units indicated (without unit symbols) corrected if necessary to two decimal places. Answer: Number of poles= ✓ Continuous power rating (kW)= Required power rating for 200% pull out torque (kW)= Percentage slip (%) = Most suitable motor from given range (kW)-
State four advantages of a pre-engaged starter when compared with an inertia type.
Knowledge Booster
Background pattern image
Mechanical Engineering
Learn more about
Need a deep-dive on the concept behind this application? Look no further. Learn more about this topic, mechanical-engineering and related others by exploring similar questions and additional content below.
Similar questions
SEE MORE QUESTIONS
Recommended textbooks for you
Text book image
Understanding Motor Controls
Mechanical Engineering
ISBN:9781337798686
Author:Stephen L. Herman
Publisher:Delmar Cengage Learning
Text book image
Refrigeration and Air Conditioning Technology (Mi...
Mechanical Engineering
ISBN:9781305578296
Author:John Tomczyk, Eugene Silberstein, Bill Whitman, Bill Johnson
Publisher:Cengage Learning
Text book image
Electrical Transformers and Rotating Machines
Mechanical Engineering
ISBN:9781305494817
Author:Stephen L. Herman
Publisher:Cengage Learning
Text book image
Automotive Technology: A Systems Approach (MindTa...
Mechanical Engineering
ISBN:9781133612315
Author:Jack Erjavec, Rob Thompson
Publisher:Cengage Learning
Mechanical Design (Machine Design) Clutches, Brakes and Flywheels Intro (S20 ME470 Class 15); Author: Professor Ted Diehl;https://www.youtube.com/watch?v=eMvbePrsT34;License: Standard Youtube License